概述
With TeleControl Basic, low-cost solutions for monitoring andcontrolling telecontrol stations /Remote Terminal Units can be set up based onSIMATIC S7-1200, SIMATIC ET 200SP and the compacttelecontrol stations of the SIMATIC family RTU3000C. Up to5 000 Remote Terminal Units / RTUs cancommunicate securely and efficiently via mobile wireless – 5G,LTE/4G, UMTS/3G and GPRS/2G – and Ethernet/Internet with thecentral control center as well as with each other.
优势
Low-cost connection of telecontrol stations via mobile wirelessand Ethernet/the Internet to the control center
Saving of costs for design and maintenance of your own wirelesssystem by using existing mobile wireless networks or theInternet
Low-cost mobile wireless volume tariffs reduce the monthlyconnection charges
Flexibility in the choice of communication paths due to supportby standard Ethernet / RJ45
Secure connection over public networks thanks to encrypted datatransfer. The management platform SINEMA Remote Connect isavailable for easy management of a large number of VPNconnections.
Support for bidirectional connections
Between station and control center
Between station and station
Remote maintenance and remote programming of the telecontrolstations during operation
应用
TeleControl Basic is based on SIMATIC S7-1200, ET 200SP as well asSIMATIC RTU3000C and secure transmission via mobile wireless or theInternet. It is particularly suitable wherever small dataquantities have to be transmitted over wireless connections or viathe Internet.
TeleControl Basic can be used as a low-cost fault signaling system,but thanks to the bidirectional communications facility, it is alsosuitable for simple telecontrol tasks for monitoring andcontrol.
Depending on the performance level of the CPU in the substations,local automation tasks are handled in addition tocommunication.
Main applications are the monitoring and control of non-mobilestations in the following sectors:
Water and wastewater
Drinking water purification and distribution
Irrigation systems
Oil and gas supplies
District heating networks
Automatic machines
Traffic control systems
Building monitoring
Weather stations
Lighthouses
Wind farms
Photovoltaic plants
Environmental monitoring equipment
Intelligent advertising panels
In addition, TeleControl Basic can also be used to link mobilestations if central monitoring and/or control is required forthese:
Railway vehicles
Special vehicles
Local public transport
Complex building machines
Ships on rivers and in coastal areas
Buoy tracking
设计
Components:
CP1243-7 LTE communications module
communications processor for LTE communication (EU and US) forsetting up telecontrol stations of the type S7-1200CP1242-7 GPRS communications module
communications processor for GPRS and GSM communication for settingup telecontrol stations of the type S7-1200CP1243-1 communications module
communications processor for setting up telecontrol stations of thetype S7-1200 for connection to the Internet using external routers,such as SCALANCE M812-1CP1542SP-1 IRC communications module
communications processor for setting up substations of the type ET200SP for connection to the Internet using external routers e.g.SCALANCE M812-1 SIMATICRTU3000C telecontrol stationsSIMATIC RTU3030C/RTU3031C and RTU3041C telecontrol station
Compact telecontrol station for energy self-sufficient applicationsfor UMTS/3G communication or LTE-M/NB-IoT communicationSIMATIC RTU3010C telecontrol station
Compact telecontrol station for energy self-sufficient applicationsfor connection to the Internet via an external router, e.g.SCALANCE M812-1TeleControl ServerBasic
software package consisting of:OPC UA server software for the PC control center;
for data exchange with an OPC client, e.g. WinCC, PCS 7 orWinCC OAConnection manager for the PC control center;
for establishing a secure telecontrol connection with the RTU formonitoring these connections and for data routing with direct datatransmission between telecontrol stations
功能
Communication options with TeleControl Basic
Processdata communication
TeleControl Server Basic software enables the connection of up to5 000 telecontrol stations to the control center via the OPCinterface (OPC UA) using GPRS mobile wireless orEthernet/internet.
TeleControl Server Basic is an OPC server software with specialcommunication functions, which permit it to support connections toremote telecontrol substations. These PLCs are configured with theCP 1243-7 LTE, CP 1242-7 GPRS, CP 1243-1 (Ethernet), CP 1542SP-1IRC (Ethernet), or they comprise the compact Remote Terminal Unitsof the RTU3000C family. Mobile wireless services or standard IPservices via Ethernet are used for the connections.
Via the mobile wireless connections or Ethernet/internet, theremote TeleControl substations can communicate with the TeleControlServer Basic software or with other SIMATIC PLCs that are connectedwith TeleControl Server Basic
The PC on which TeleControl Server Basic is installed must bepermanently accessible from the mobile wireless network. It musttherefore be directly connected to the mobile wireless providerusing a dedicated line, and permanently to the internet, e.g. viaDSL.
For substations of the type S7-1200 and ET 200SP, the telecontrolfunctions are configured directly with STEP 7 Basic/ProfessionalV14 (TIA Portal) or higher. The Remote Terminal Units of theRTU3000C family are configured via a web server (web-basedmanagement – WBM).
Alarmsas text messages
The communications processors CP 1243-7 LTE, CP 1242-7 GPRS and theRTU3000C can receive and send messages directly as text messages. Acell phone or another PLC can be the communication partner.
Wake-upfunction
"Wake-up" of stations that change from standby mode to online modefor diagnostics purposes. The RTU3000C is woken up by itscommunication partner (e.g. TeleControl Server Basic) using awake-up call or a wake-up SMS to establish the connection betweenthem.
For security reasons, the communication partner must identifyitself appropriately for the wake-up function, e.g. using the CLIPfunction.
Accessto the telecontrol stations using teleservice
TeleControl Server Basic contains the teleservice function directlyin the TIA Portal. This gives internationally active plant andmachine manufacturers worldwide access to the SIMATIC telecontrolstations.